Attic Ventilation Calculator
Net free area, feet of ridge vent and intake vents, from the IRC's base ratio or its exception.
By Marko Visic, BSc Physics · Updated November 25, 2026
Code ratio 1/150 [1]: the default, and the lower ratio needs the upper-vent arrangement as well.
Required net free area: 1,440 sq in (10 sq ft) [1]1,500 ÷ 150 × 144 = 1,440 sq in; 1,500 ÷ 150 = 10 sq ft
At 1/150 [1] the code sets no intake and exhaust split; the tool starts at 50 % exhaust, and you can change it.
Exhaust (ridge): 40 lin ft of Air Vent ShingleVent IIexhaust 1,440 × 0.5 = 720 sq in; 720 ÷ 18 = 40 → 40 lin ft [2]
Intake (soffit/eave): enter an intake NFA per vent (from the product's label)intake 1,440 × (1 − 0.5) = 720 sq in. No intake product is verified here.
The code also requires an air gap at the vents between the insulation and the sheathing, and sets condensation-control rules for an unvented attic instead; see the method and sources below, and ice dams for the cold-climate eave inlet.
The 1/150 rule is the code: the 2024 IRC requires 1/150 of the vented space in net free vent area.[1] The lower 1/300 is an exception, allowed only when the vents are split with upper vents near the ridge and, in cold zones, a vapor retarder is on the ceiling.[1] This tool defaults to the code and shows the equation.

Drawing: CalculateMyRoof · CC BY 4.0 · How to reuse
How it works, and the 1/150 rule
Net free area (NFA) is the open area air can actually pass through. The 2024 IRC R806.2 sets the vent area at 1/150 of the vented space: divide the attic floor by that ratio for square feet, or convert to square inches.[1] The 2024 IRC allows the lower 1/300 only when both conditions are met: 40-50% of the vent area in upper vents within 3 ft of the ridge with the rest in the bottom third, and, in climate zones 6-8, a Class I or II vapor retarder on the warm-in-winter side of the ceiling.[1]
Split the required NFA into intake and exhaust. Under the exception the split must be 40-50% upper;[1] under the base ratio the code sets no split, so the tool starts at 50 % exhaust and you can change it. Divide the exhaust share by a ridge vent's net free area per linear foot for the feet of ridge vent, and the intake share by a vent's rated NFA for the count. Air Vent's ShingleVent II is 18 sq in per lineal ft; the II-7 and II-9/9A are 16 sq in per lineal ft.[2] Keep at least a 1 in air gap between the insulation and the sheathing at the vents (R806.3).[1]
Common questions
How do I calculate attic venting?
The net free vent area is the attic floor area × 144 ÷ the ratio. At 1/150 a 1,000 sq ft attic needs 1,000 ÷ 150 × 144 = 960 sq in (1,000 ÷ 150 = 6.67 sq ft); split it intake and exhaust, then divide by each vent's NFA.[1]
What is the 1/150 rule for attic ventilation?
It is the IRC's base ratio: 1/150 of the vented space in net free vent area.[1] The 1/300 ratio halves that but applies only when the upper-vent arrangement is used and, in climate zones 6-8, a vapor retarder is present.[1]
How many roof vents for a 1,000 sq ft house?
It is the attic floor area that counts, not the house's total floor on more than one story. A 1,000 sq ft attic needs 1,000 ÷ 150 × 144 = 960 sq in (1,000 ÷ 150 = 6.67 sq ft) under the code, or 1,000 ÷ 300 × 144 = 480 sq in (1,000 ÷ 300 = 3.33 sq ft) under the exception.[1]With a balanced split the exhaust is half that, 480 × 0.5 = 240 sq in: 240 ÷ 18 = 13.33 → 14 lin ft of ShingleVent II, or 240 ÷ 16 = 15 → 15 of the II-7 or II-9; the vent count depends on each vent's labeled NFA.[1][2]
How much venting for an 1,150 sq ft attic?
1,150 ÷ 150 × 144 = 1,104 sq in under the code, or 1,150 ÷ 300 × 144 = 552 sq in under the exception.[1]
Unvented attics
The code also allows an unvented attic instead, sealed and insulated, with condensation-control insulation from R-5 in the mildest climate zone to R-35 in the coldest (R806.5).[1] In cold climates, sizing the eave inlet to keep the deck cold is a separate method; see ice dams, where CRREL's worked example needs 14.6 sq in of inlet per running foot in total, 7.3 at each eave.[3]
Methodology & sources
The ratios and conditions are the 2024 IRC R806, verified in October 2026; the ridge-vent net free areas are ICC-ES ESR-2071. No intake product is verified here, so its NFA is the figure you enter, and the page quotes no prices. Every build re-runs the engine against the worked vectors and checks each printed number against the facts.
Sources
- [1] International Code Council. 2024 International Residential Code, Chapter 8: Roof-Ceiling Construction (Oct 2026 version). Sections R806.2, R806.3, R806.5. Retrieved Oct 28, 2026. codes.iccsafe.org
- [2] ICC Evaluation Service. ESR-2071, Air Vent ShingleVent II (reissued June 2026). Retrieved Oct 9, 2026. icc-es.org
- [3] U.S. Army ERDC-CRREL (Tobiasson, Buska and Greatorex). Guidelines for Ventilating Attics and Cathedral Ceilings to Avoid Icings at Their Eaves, Buildings VIII (2001). Retrieved Oct 14, 2026. web.ornl.gov
Change log: first published November 25, 2026.